CVE-2026-61884: The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to s
CVE-2026-61884 is a critical-severity flaw (CVSS 9.8) affecting affected software. Below: why it ranks where it does, which versions are affected, what to do, and the exact commands.
The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settin
Why this priority
- Critical severity
- CISA SSVC: automatable with total technical impact
- Remotely exploitable, no login, no user action
A fixed release or distro patch exists.
Risk facts
| CVSS score | 9.8 (Critical) |
| Attack vector | Network (remote) |
| Attack complexity | Low |
| Privileges needed | None |
| User interaction | None |
| EPSS exploit chance | 0.6% (top 54%) |
| CISA exploited list | No |
| Weakness | CWE-306 |
| Published | 2026-07-24 |
| Last modified | 2026-10-24 |
Last updated 2026-10-24 · Sources: CVE Program, NVD, CISA KEV, EPSS and vendor advisories · How we score
Timeline
- Published CVE record published
- Updated Record last modified
Exact fixes by distribution
Scores and fixes here are computed automatically from those and other public sources. Confirm with the vendor advisory before changing production systems.
Quick answers
How do I fix CVE-2026-61884?
No fixed release is listed yet. Watch the vendor advisory and apply any mitigation shown on this page.
Is CVE-2026-61884 being exploited?
CVE-2026-61884 is not on the CISA Known Exploited Vulnerabilities list at the time of the last update. Check again, as this can change.
What does CVE-2026-61884 affect?
CVE-2026-61884 affects affected software. Severity is critical (CVSS 9.8). The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface wi
How urgent is CVE-2026-61884?
Priority 54/100. Critical severity; CISA SSVC: automatable with total technical impact; Remotely exploitable, no login, no user action